How do you coordinate with the company doing the fire suppression?
They cross at four specific points, and those are the ones to close off before starting. One: the signal from the flow switch or the pressure switch of the sprinkler installation reaches our control panel and is treated as an alarm, with its own text and its own zone. Two: the state of the valves and of the pump set —stopped, running, fault— is brought to the panel as well, so that a fault on the water side does not go unnoticed for months. Three: the electrical supply to the pump set and its supervision. And four: the interlocks, above all shutting down the air conditioning.
That is agreed in a meeting with the fire suppression installer and with whoever is running the site, and it is written into the cause and effect table. What cannot happen is that each one hands over their part separately and the first time they are tested together is the day of the inspection.
Who is responsible for what is worth writing down too. We sign off our part and demonstrate that the signal arrives and is read correctly; the hydraulic calculation, the pressure test and the certificate for the water installation are signed by whoever did it. Each signature covers its own, and that protects the client more than a single point of contact who cannot answer for half of it.
Where it is set out in full.
On the same topic.
All the questions.
Five hundred and forty-four, grouped by topic. Each with its own page.
Get started
See it working.
A written answer is enough to decide whether it interests you. To know whether it works at your site you have to see it on a real scene, with the image as it is and, on top of it, what the system understands from it. That is on the IRIS Neural website, which is the group's product.