How many zones and how many devices fit, and what if I want to extend it?

A zone is the piece of building the control panel points to as the origin of the alarm; a loop is the two-wire cable that leaves the control panel, runs round the addressable devices and comes back to it. On a conventional panel, zone and cable are the same thing. On an addressable one they are different things: devices from several zones sit on the same loop, and the zones are defined by programming.

The criteria for splitting them are given by UNE 23007-14 and they can be checked: a zone should not go beyond about 1,600 m², it should not span more than one storey except in very small buildings, and inside it you should not have to walk more than about 30 m to find the device that has gone off. Vertical shafts —stairs, risers, lifts— are treated as a separate zone. As for the loop, each manufacturer declares how many devices it takes, and in practice it is filled well below that number to leave headroom, spreading short-circuit isolators so that one badly driven screw takes out a section and not the whole storey.

Extending depends on three things: whether there is capacity left in loops and cards, whether the manufacturer is still supplying devices compatible with that version and —the one always forgotten— whether the batteries still give the standby time the documentation says, because every new device draws current. When the control panel can take no more, the alternative is not always to throw it all out: you can add a new panel on the network and replace it in phases.

All the questions.

Five hundred and forty-four, grouped by topic. Each with its own page.

Get started

See it working.

A written answer is enough to decide whether it interests you. To know whether it works at your site you have to see it on a real scene, with the image as it is and, on top of it, what the system understands from it. That is on the IRIS Neural website, which is the group's product.